The Vermont Department of Health (Health) and Department of Environmental Conservation (DEC) have reviewed the results of recent indoor air sampling for PCBs at Bellows Free Academy (St Albans).

PCBs were detected, but no applicable Vermont School Action Level was exceeded. Sampling details are outlined:

No tested room or space had PCB levels at or above the applicable Vermont School Action

Level. At least one detected level was between 75-100 ng/m3 and these space(s) require

additional indoor sampling. The lowest grade in your school is 9th grade. Therefore, 100 ng/m3

is the Vermont School Action Level for your school. The results are provided below.

Tested rooms and spaces are listed below. Rooms and spaces not listed were not tested. Not

detected means that the laboratory did not detect any PCBs. Spaces with results within 25% of

your school’s Vermont School Action Level are bolded in the table below.

The Vermont School Action Levels are:

• 30 ng/m3 (nanograms per cubic meter) for pre-kindergarten

• 60 ng/m3 for kindergarten through 6th grade

• 100 ng/m3 for 7th grade through adult

Room or Space Result (ng/m3)

E Building Basement 77

B114 Storage 37

Auto Shop 23

Room or Space Result (ng/m3)

B118 Storage 14

C109 Storage 11

C109 Elevator Room 10

B115 9

C111 7

IDF115 6

B110 Suite 6

B123 Main Office 6

B103 6

A126 6

B210 5

W117A 5

B120A 5

E405-Real Life Storage 5

B109 5

A111 5

E204A 5

W100-300 Stair 5

A220 5

B201A 5

A122 Mech. 5

A301 5

B111 5

E400-Hall 5

E500 5

A325 4

B122 Woodshop 4

E500a 4

E204 4

B117 4

A208 4

C Hall 2nd Floor 4

E406 4

A114 File Room 3

W205 3

3rd Floor Hall (A Build) 3

A219 3

A108 3

A121 3

A317 3

B112B 3

Snack Bar Lobby 3

Room or Space Result (ng/m3)

A104 3

Gym (B201) 3

B204 Storage 2

E502/E502A 2

3rd Floor girls BR 2

A211 2

A308 2

1st Floor Boys Bathroom (A

Building) Not detected

1st Floor Main Room Not detected

A Main Entrance Not detected

A100 Hall Not detected

A112A Not detected

A116 Not detected

A116A Not detected

A120/121A Not detected

A122 Not detected

A127 Suite Not detected

A201 Not detected

A206/205 Not detected

A213 Not detected

A215 Not detected

A218 Not detected

A314 Not detected

A320 Not detected

Ambient (Outside C Building) Not detected

B Lobby Not detected

B101 Mail Room Not detected

B102C Not detected

B113 Not detected

B200 Hallway Not detected

B205 Locker Room Not detected

B205 Weight Room Not detected

B206 Not detected

B207 Not detected

C103 Womens Rm Not detected

C107A Not detected

C203 Not detected

C204 Classroom Not detected

C205 Suite Not detected

C208 Not detected

E202 Not detected

Room or Space Result (ng/m3)

E203A Storage Not detected

E301 Conference Not detected

E301 Principal Not detected

E302/303-Café Not detected

E302D Kitchen Office Not detected

E302E-dishroom suite Not detected

E304 Boys BR Not detected

E304B-1 Not detected

E304B-Assistant Principal Not detected

E403a Not detected

E501 Dark Room Not detected

FB-01 Not detected

Girls Ref Room Not detected

Kitchen BR Not detected

Library Not detected

Main 1st Floor Not detected

Mezzanine (above library) Not detected

Upstairs C Boys Not detected

W100 Hallway Not detected

W104 Not detected

W106 Not detected

W109 Not detected

W110 Not detected

W112 mens Not detected

W114(elevator control room) Not detected

W116B Not detected

W117 Boiler Room Not detected

W200 Hallway Not detected

W202 Not detected

W207 Not detected

W208 Not detected

W210 Not detected

W301 Not detected

W302 Not detected

W304-Nurse Not detected

W305 Not detected

W308 Not detected

W310B Not detected

W310c Not detected

Weight Room Storage 1 Not detected

What about the rooms that were not tested?

Before testing, the consultant evaluated the school building for potential PCB sources and

assigned rooms to groups based on the presence of similar building materials, construction

and/or renovation dates. About one third of rooms in each group were tested. Rooms that

were not tested are assumed to have similar PCB levels as the tested rooms in that same group.

What happens next?

Additional action will be required by DEC in the bolded rooms in the table above. Additional

indoor air sampling is required to monitor fluctuations of PCB indoor air levels for spaces within

25% of your school's action level to ensure they do not exceed the School Action Level.

No occupancy changes are required at this time. However, if the use of a classroom changes,

then these results need to be evaluated for the new use. For example, if the space is currently

used for grades 7-12 and it needs to be used for a lower grade level, then the results need to be

evaluated for the school action level for that age group.